Continuous level measurement
Ultrasonic / Ultrasonic transmitters / SITRANS LU180
4/214
Technical specifications
SITRANS LU180
Mode of operation
Measuring principle Ultrasonic level measurement
Input
Measuring range 0.25 ... 5 m (0.8 ... 16.4 ft)
Frequency 54 kHz
Output
mA 4 ... 20 mA
•
Span Proportional/ inversely proportional
•
Max. load 600 Ω in the loop at 24 V DC
Power supply
Supply voltage 12 ... 30 V DC, 0.1 A surge
Max. power consumption 0.75 W (25 mA at 24 V DC)
Certificates and approvals CSAIS/ ClassI,II,III, Div.1,
Groups:A,B,C,D,E,F,G T4
FMIS/ ClassI,II,III, Div.1,
Groups:A,B,C,D,E,F,G T4
ATEXII1GExiaIICT4Ga, Ta=
‑40°Cto+60°C;
UKEXII1GExiaIICT4Ga, Ta=
‑40°Cto+60°C;
IECExExiaIICT4Ga, Ta= ‑40 °Cto+60°C;
NEPSIExiaIICT4Ga
Accuracy
Error in measurement 0.25 % of measuring range (in air)
Resolution 3 mm (0.125 inch)
Temperature compensation Built in
Echo processing Sonic Intelligence
Rated operation conditions
Beam angle 12°
Ambient temperature
•
Standard -40 ... +60 °C (-40 ... +140 °F)
•
Metallic mounting -20 ... +60 °C (-4 ... +140 °F)
Storage temperature
•
Standard -40 ... +60 °C (-40 ... +140 °F)
•
Metallic mounting -20 ... +60 °C (-4 ... +140 °F)
Max. static operating pressure Normal atmospheric pressure
Design
Weight 1.3 kg (2.9 lb)
Material
•
Electronics enclosure PBT
•
Transducer PVDF copolymer
Degree of protection IP68 / NEMA 6 / TYPE 6
Process connection
•
2" NPT [(Taper), ASME B1.20.1]
•
R 2" [(BSPT), EN 10226]
•
G 2" [(BSPP), EN ISO 228-1]
•
4" sanitary
Flange adapter 3" Universal (fits DN 65, PN 10 and 3"ASME)
Cable inlet 1 inlet for M20, optional 1/2" NPT
Options
SITRANS
LU180
Optional
flange
adapter
The SITRANS LU180 can be fitted with the optional 75 (3)
flange adapter for mating to 3" ASME, DIN 65 PN10 and
JIS 10K3B flanges.
SITRANS LU180, Flange Adapter
SITRANS LU180 optional flange adapter, dimensions in mm (inch)