Overview
MultiRanger 200 HMI
MultiRanger 200 HMI
4/1
Overview
MultiRanger 200 HMI is a versatile short to medium-range ultrason
ic single and multi-vessel level monitor/controller for virtually any
application in a wide range of industries.
Benefits
Easy to use HMI display with local four-button programming,
menu-driven parameters, and Wizard support for key applications
English, German, French, Spanish, Chinese, Italian, Portuguese,
and Russian texts on the HMI
Removable terminal blocks for ease of wiring
Digital input for back-up level override from point level device
Communication using built-in Modbus RTU via RS 485 and SIMAT
IC PDM configuration software
Compatible with SmartLinx system: PROFIBUS DP, PROFINET (cyc
lic access of process values only), DeviceNet, Modbus TCP/IP, and
EtherNet/IP
Single or dual point level monitoring
Auto False-Echo Suppression for fixed obstruction avoidance
Differential amplifier transceiver for common mode noise reduc
tion and improved signal-to-noise ratio
Level, volume, and flow measurements in open channels, differ
ential control, extended pump control, and alarm functions
Wall and panel mounting options
Application
MultiRanger 200 HMI can be used with various materials, including,
water, municipal waste, acids, woodchips, or on materials with high
angles of repose. MultiRanger 200 HMI offers true dual point monit
oring, digital communications with built-in Modbus RTU via RS 485,
as well as compatibility with SIMATIC PDM, allowing PC configura
tion and set-up. MultiRanger 200 HMI features Sonic Intelligence
advanced echo-processing software for increased reading reliability.
MultiRanger 200 HMI will monitor open channel flow and features
more advanced relay alarming and pump control functions as well
as volume conversion.
It is compatible with chemical-resistant EchoMax transducers that
are approved for hostile environments.
Key Applications: wet wells, flumes/weirs, bar screen control, hop
pers, chemical storage, liquid storage, crusher bins, dry solids stor
age
Design
The MultiRanger 200 HMI is available in wall or panel mounting
options.
MultiRanger 200 HMI · 2023
© Siemens AG 2023
MultiRanger 200 HMI
4/2
Selection and ordering data
Article No.
MultiRanger 200 Ultrasonic level controller
Continuous, non-contact, 15m (50ft) range. Monitors level,
volume, and open channel flow in liquids, slurries, and solids.
7ML5033-
-
Click on the Article No. for the online configuration in the PIA Life Cycle Portal.
Versions
MultiRanger200, level, volume, flow, and differential measurements 2
Mounting, enclosure design
4buttonHMI, Wallmount, standardenclosure D
4button HMI, Wallmount, 4entries, 4M20 cable glands included E
4buttonHMI, PanelMount F
Input voltage
100...230VAC A
12...30VDC B
Number of measurement points
Single point version 0
Dual point version 1
Data communications (SmartLinx)
Without module 0
SmartLinx PROFIBUSDPV0 module 2
SmartLinx DeviceNet module 3
SmartLinx PROFIBUSDPV1 module 4
SmartLinx PROFINET module
2)
5
SmartLinx EtherNet/IP module 6
SmartLinx Modbus TCP/IP module
See SmartLinx product page for more information.
7
Output relays
6relays (4FormA, 2FormC), 250VAC 2
Approvals
Ordinary Locations/General Purpose (Non-Ex), CE, UKCA, FM,
C
CSA
US
, UL Listed, RCM, EAC,
KC
A
CSA ClassI, Div.2, GroupsA,B,C,andD; ClassII, Div.2, GroupsFandG; ClassIII
1)
B
1)
Available with Mounting/Enclosure design optionsDorE.
2)
SmartLinx PROFINET module is certified per standard V2.2.4.
Selection and Ordering data Order code
Further designs
Please add "-Z" to Article No. and specify Order code(s).
Stainlesssteeltag [69x50mm (2.71x1.97inch)]: Meas
uring-point number/identification (max.27characters)
specify in plain text
Y15
Declaration of compliance 2.1 (EN 10204) - delivery meets
order requirements
C11
Spare parts and accessories Article No.
Operating Instructions
All literature is available to download for free, in a range
of languages, at
http://www.siemens.com/processinstrumentation/docu
mentation
Optional equipment
Tag, stainlesssteel, 12x45mm, one text line, suitable for
enclosures
7ML1930-1AC
Sunshield, 304Stainlesssteel
7ML1930-1GA
SITRANSRD100, loop powered display - seeChapter7
7ML5741-...
SITRANS RD150, remote digital display for 4 ... 20 mA and
HART devices - see Chapter 7
7ML5742-.....-....
SITRANSRD200, universal input display with Modbus con
version - seeChapter7
7ML5740-...
SITRANSRD300, dual line display with totalizer and linear
ization curve and Modbus conversion - seeChapter7
7ML5744-...
MultiRanger 200 HMI · 2023
© Siemens AG 2023
MultiRanger 200 HMI
4/3
Selection and ordering data (continued)
Spare parts and accessories Article No.
Spare parts
Power Supply Board (100...230VAC)
7ML1830-1MD
Power Supply Board (12...30VDC)
7ML1830-1ME
Removable terminal blocks
A5E38824197
Spare lid with HMI, MultiRanger200HMI/HydroR
anger200HMI, wall
A5E35778738
Spare lid with HMI, MultiRanger200HMI/HydroR
anger200HMI, panel
A5E35778740
SmartLinx DeviceNet module
7ML1830-1HT
SmartLinx PROFIBUSDPV1 module
A5E35778741
Smartlinx PROFINETIO module
7ML1830-1PM
SmartLinx ModbusTCP/IP, EtherNet/IP module
7ML1830-1PN
Technical specifications
MultiRanger 200 HMI
Mode of Operation
Measuring principle Ultrasonic level measurement
Measuring range 0.3 ... 15 m (1 ... 50 ft)
Measuring points 1 or 2
Input
Analog 0 ... 20 mA or 4 ... 20 mA, from alternate
device, scalable
Discrete 10 ... 50 V DC switching level Logical 0 ≤ 0.5
V DC Logical 1 = 10 ... 50 V DC max. 3 mA
Output
EchoMax transducer 44 kHz
Ultrasonic transducer Compatible transducers: ST-H and EchoMax
series XPS-10, XPS-15/15F, and XRS-5
Relays Rating 5 A at 250 V AC, non-inductive
mA output 0 ... 20 mA or 4 ... 20 mA
Max. load 750 Ω, isolated
Resolution 0.1 % of range
Accuracy
Error in measurement
0.25% of range or 6mm (0.24inch),
whichever is greater
±4mm (0.16inch) in combination with
an XRS-5 transducer on ranges 4m (13ft)
or less
Resolution 0.1 % of measuring range
1)
or 2 mm (0.08
inch), whichever is greater
Temperature compensation
-50 ... +150 °C (-58 ... +302 °F)
Integral temperature sensor
External TS-3 temperature sensor (option
al)
Programmable fixed temperature values
Rated operating conditions
Installation conditions
Location Indoor/outdoor
Installation category II
Pollution degree 4
Ambient conditions
Ambient temperature (housing) -20...+50°C (-4...+122°F)
Storage temperature -20...+50°C (-4...+122°F)
Design
Weight
Wall mount 1.22 kg (2.68 lb)
Panel mount 1.35 kg (2.97 lb)
Material (enclosure) Polycarbonate
Degree of protection (enclosure)
Technical specifications (continued)
MultiRanger 200 HMI
Wall mount IP65/Type 4X/NEMA 4X
Panel mount IP54/Type 3/NEMA 3
Electrical connection
Transducer and mA output signal 2-core copper conductor, twisted, shielded,
0.5...0.75mm² (22...18AWG), Belden
8760 or equivalent is acceptable
Max. separation between transducer and
transceiver
365 m (1 200 ft)
Displays and controls 60 x 40 mm (2.36 x 1.57 inch) LCD 240 x
160 pixels resolution
Power supply
AC version 100 ... 230 V AC ± 15 %, 50/60 Hz, 36 VA (17
W)
DC version 12 ... 30 V DC (20 W)
Certificates and approvals
CE, UKCA, RCM, EAC, KC
2)
FM,
C
CSA
US
, UL listed
CSA Class I, Div. 2, Groups A, B, C, D, Class
II, Div. 2, Groups F, G, Class III (wall mount
only)
Communication
RS 232 with Modbus RTU or ASCII via
RJ-11 connector
RS 485 with Modbus RTU or ASCII via ter
minal strips
Optional: SmartLinx cards for
-
PROFIBUS DP-V1, PROFINET (cyclic
access of process values only)
-
DeviceNet, Modbus TCP/IP, EtherNet/IP
1)
Program range is defined as the empty distance to the face of the trans
ducer plus any range extension
2)
EMC performance available on request
MultiRanger 200 HMI · 2023
© Siemens AG 2023
MultiRanger 200 HMI
4/4
Dimensional drawings
Panel mount dimensions
Wall mount dimensions
Lid screws
(6)
Cable entry
location
Ø4.3 (0.17),
four mounting holes
Enclosure
lid
Cable
entry
Enclosure
base
198 (7.8)
278 (10.9)
31
(1.2)
94
(3.7)
15
(0.6)
240 (9.4)
161 (6.3)
87 (3.4) 131 (5.2)
15
(0.6)
6
(0.2)
228 (9.0)
MultiRanger 200 HMI, dimensions in mm (inch)
MultiRanger 200 HMI · 2023
© Siemens AG 2023
MultiRanger 200 HMI
4/5
Circuit diagrams
Note:
1.
Use 2-core copper wire, twisted, with shield, for expansion up to
365 m (1 200 ft). Route cable in grounded metal conduit, separate
from other cables.
2.
Verify that all system components are installed in accordance with
instructions.
3. Connect all cable shields to the MultiRanger shield connections.
Avoid differential ground potentials by not connecting cable shields
to ground (earth) anywhere else.
4. Keep exposed conductors on shielded cables as short as possible
to reduce noise on the line caused by stray transmissions and noise
pickup.
Relays shown in released
state
DC version
See note 1
DISCRETE
INPUTS
SHIELD
mA INPUT
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Relay 6
SHIELD
SYNC
4 ... 20 mA
OUTPUTS
Or
COM
A
B
RS 485
TS-3
1
2
-
+
-
+
L1L2/N
12 ... 30 V
TB2
TB3
TB1
TB1
- +
1
2
1
2
-
+
-
+
-
+
-
+
MultiRanger 200 HMI connections
MultiRanger 200 HMI · 2023